UKOOA FM / FP TYPE 150/250V Fire Resistant Offshore & Marine Instrumentation Cables
Applications
- BS 6883/BS 7917/UKOOA FM / FP TYPE 150/250V Fire Resistant Offshore & Marine Instrumentation Cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required
Standards
- BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2
Construction
Conductor | Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228. |
---|---|
Fire Protection | Mica glass tape |
Insulation | EPR complying with BS7655 GP4? |
Drain Wire | Tinned copper drain wire? |
Collective Screen | Collective Screen |
Bedding | CSP ?C SW2 compound complying with BS 7655? |
Armour? | Galvanised steel wire braid to BS 6883? |
Outer Sheath? | CSP ?C SW2 compound complying with BS 7655 (TYPE FL: Blue; TYPE FN: Grey). |
Dimensions and Weight
Construction No. of cores??Cross section(mm2) |
Nominal Insulation Thickness mm |
Nominal Thickness of Inner Sheath mm |
Nominal Thickness of Outer Sheath mm |
Nominal Overall Diameter mm |
Approx. Weight kg/km |
---|---|---|---|---|---|
3??2??0.75 | 0.8 | 1.2 | 1.4 | 18.6 | 580 |
7??2??0.75 | 0.8 | 1.4 | 1.6 | 23.2 | 915 |
12??2??0.75 | 0.8 | 1.6 | 1.8 | 29.7 | 1420 |
20??2??0.75 | 0.8 | 2.1 | 2.7 | 40.1 | 2905 |
3??3??0.75 | 0.8 | 1.3 | 1.5 | 20.4 | 700 |
7??3??0.75 | 0.8 | 1.5 | 1.7 | 26.6 | 1180 |
12??3??0.75 | 0.8 | 1.9 | 2.2 | 38.5 | 2550 |
1??4??0.75 | 0.8 | 1.2 | 1.3 | 14.6 | 360 |
1??2??1.0 | 0.8 | 1.0 | 1.2 | 13.0 | 295 |
1??3??1.0 | 0.8 | 1.0 | 1.2 | 13.6 | 330 |
1??4??1.0 | 0.8 | 1.0 | 1.3 | 15.9 | 380 |
3??2??1.5 | 0.8 | 1.3 | 1.4 | 21.6 | 732 |
7??2??1.5 | 0.8 | 1.4 | 1.6 | 27.8 | 1242 |
12??2??1.5 | 0.8 | 1.7 | 1.9 | 36.4 | 2039 |
3??3??1.5 | 0.8 | 1.3 | 1.5 | 24.5 | 780 |
7??3??1.5 | 0.8 | 1.5 | 1.7 | 32.1 | 1409 |