UKOOA KH/KK TYPE 150/250V Flame Retardant Offshore & Marine Instrumentation Cables
Applications
- BS 6883/BS 7917/UKOOA KH/KK TYPE 150/250V Offshore & Marine Instrumentation Cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required
Standards
- BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2
Construction
Conductor | Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228. |
---|---|
Fire Protection | Mica glass tape |
Insulation | EPR complying with BS7655 GP4? |
Drain Wire | Tinned copper drain wire? |
Collective Screen | Collective Screen |
Bedding | EVA - SW4 compound complying with BS 7655? |
Armour? | Galvanised steel wire braid to BS 6883? |
Outer Sheath? | EVA - SW4 compound complying with BS 7655 (TYPE KH: Blue; TYPE KK: Grey). |
Dimensions and Weight
Construction No. of cores??Cross section(mm2) |
Nominal Insulation Thickness mm |
Nominal Thickness of Inner Sheath mm |
Nominal Thickness of Outer Sheath mm |
Nominal Overall Diameter mm |
Approx. Weight kg/km |
---|---|---|---|---|---|
1??2??0.75 | 0.8 | 1.0 | 1.2 | 11.5 | 230 |
3??2??0.75 | 0.8 | 1.2 | 1.4 | 16.5 | 430 |
7??2??0.75 | 0.8 | 1.4 | 1.6 | 21.0 | 720 |
12??2??0.75 | 0.8 | 1.6 | 1.8 | 27.0 | 1110 |
1??3??0.75 | 0.8 | 1.0 | 1.2 | 12.0 | 245 |
3??3??0.75 | 0.8 | 1.3 | 1.5 | 18.5 | 530 |
7??3??0.75 | 0.8 | 1.5 | 1.7 | 23.5 | 900 |
12??3??0.75 | 0.8 | 1.7 | 2.0 | 31.0 | 1530 |
1??4??0.75 | 0.8 | 1.2 | 1.3 | 13.5 | 310 |
1??2??1.0 | 0.8 | 1.0 | 1.2 | 12.0 | 240 |
3??2??1.0 | 0.8 | 1.3 | 1.4 | 17.0 | 490 |
1??3??1.0 | 0.8 | 1.1 | 1.2 | 12.5 | 285 |
1??4??1.0 | 0.8 | 1.2 | 1.4 | 14.0 | 340 |
1??2??1.5 | 0.8 | 1.1 | 1.2 | 12.5 | 290 |
3??2??1.5 | 0.8 | 1.3 | 1.5 | 18.5 | 560 |
1??3??1.5 | 0.8 | 1.1 | 1.2 | 13.0 | 320 |
1??4??1.5 | 0.8 | 1.2 | 1.4 | 14.5 | 370 |
20??2??1.5 | 0.8 | 2.0 | 2.3 | 38.0 | 2430 |